Image is for illustration purposes only.
Baudouin Generators
Baudouin 44 kVA Diesel Generator
The Baudouin 44 kVA diesel generator delivers 44 kVA / 35.2 kW standby and 40 kVA / 32 kW prime power from a 4-cylinder BAUDOUIN 4M06G44/5 turbocharged engine, with a 400/230 V, 50 Hz three-phase output for sites that size capacity around a measured load profile.
- Standby Power (ESP)
- 44kVA· 35.2 kW
- Prime Power (PRP)
- 40kVA· 32 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 44 kVA / 35.2 kW / 64 A
- Prime Power (PRP)
- 40 kVA / 32 kW / 58 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Baudouin
- Engine Model
- 4M06G44/5
- Cylinders
- 4 / Inline
- Displacement
- 2.3 L
- Bore x Stroke
- 89 x 92 mm
- Compression Ratio
- 17.5:1
- Aspiration
- Turbocharged
- Cooling System Capacity
- 16
- Fuel Consumption (100% load)
- 9.9 L/h
- Fuel Consumption (75% load)
- 7.3 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 2000 x 950 x 1260 mm
- Open Type (L x W)
- 1700 x 950 mm
Product Information
- Category
- Baudouin Generators
- Stock Code
- NDX-BAU-44
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Baudouin 44 kVA Diesel Generator
Specifying a generator starts with one question: which rating actually matches the load profile of the site? The Baudouin 44 kVA answers it with two clearly separated figures, 44 kVA / 35.2 kW standby and 40 kVA / 32 kW prime, so backup duty during an outage and longer continuous running are never treated as the same job. At a 0.8 power factor on a 400/230 V system it supplies 64 A in standby and 58 A in prime operation, which lets cable cross-sections and switchgear be selected straight from these two values.
Engine
The set is built around the BAUDOUIN 4M06G44/5 diesel engine. It has 4 cylinders in an inline arrangement, a displacement of 2.3 L, a bore and stroke of 89 x 92 mm and a compression ratio of 17.5:1. Aspiration is turbocharged. Fuel consumption is stated as 9.9 L/h at 100% load and 7.3 L/h at 75% load, with a cooling capacity value of 16.
Alternator and Electrical Data
The alternator runs at 400/230 V and 50 Hz in a three-phase configuration with a 0.8 power factor. Insulation is class H and the protection rating is IP23. Rated current is 64 A in standby operation and 58 A in prime operation.
- Standby power (ESP): 44 kVA / 35.2 kW / 64 A
- Prime power (PRP): 40 kVA / 32 kW / 58 A
- Engine: BAUDOUIN 4M06G44/5, 4 cylinders, inline, 2.3 L
- Bore x stroke 89 x 92 mm, compression ratio 17.5:1, turbocharged
- Voltage and frequency: 400/230 V, 50 Hz, 3 phase, power factor 0.8
- Insulation class H, protection class IP23
- Fuel consumption: 9.9 L/h at 100% load, 7.3 L/h at 75% load
Installation and Operation
In canopy form the set measures 2000 x 950 x 1260 mm (L x W x H), while the open type version measures 1700 x 950 mm (L x W), so the installation layout can be planned around whichever version suits the site. The unit carries the stock code NDX-BAU-44, is of Türkiye origin and is covered by a 24-month warranty.