Image is for illustration purposes only.
Shanghai Dongfeng Generator
Shanghai Dongfeng 400 kVA Diesel Generator
Rated at 400 kVA / 320 kW standby and 360 kVA / 288 kW prime, this Shanghai Dongfeng diesel generator runs on an SDEC SC13H425D2 engine and burns 85 L/h at full load. Output is 400/230 V, 50 Hz, three phase, from a class H insulated alternator.
- Standby Power (ESP)
- 400kVA· 320 kW
- Prime Power (PRP)
- 360kVA· 288 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 400 kVA / 320 kW / 577 A
- Prime Power (PRP)
- 360 kVA / 288 kW / 520 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Shanghai Dongfeng
- Engine Model
- SC13H425D2
- Cylinders
- 6 / Inline
- Displacement
- 12.8 L
- Bore x Stroke
- 128 x 153 mm
- Compression Ratio
- 16:1
- Aspiration
- Turbocharged Aftercooled
- Cooling System Capacity
- 65
- Fuel Consumption (100% load)
- 85 L/h
- Fuel Consumption (75% load)
- 63.7 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 4000 x 1400 x 2100 mm
- Open Type (L x W)
- 3000 x 1400 mm
Product Information
- Category
- Shanghai Dongfeng Generator
- Stock Code
- NDX-SDF-400
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Shanghai Dongfeng 400 kVA Diesel Generator
The real cost of a generator is not settled at purchase; it is paid one running hour at a time. That is where the Shanghai Dongfeng 400 kVA makes its case: 85 litres per hour at full load and 63.7 litres per hour at 75 percent load, a gap of 21.3 litres for every quarter of load taken off. With 400 kVA / 320 kW standby and 360 kVA / 288 kW available continuously, the set can carry a site without being run at its ceiling.
Engine
Power comes from an SDEC SC13H425D2 diesel engine: 12.8 litres of displacement over six cylinders in an inline arrangement. A 128 mm bore works against a 153 mm stroke, giving a long-stroke layout, and the compression ratio is 16:1. Air is fed through a turbocharged, aftercooled intake, and it is this combustion arrangement that sits behind the fuel figures above.
Alternator and Electrical Data
The alternator delivers 400/230 V at 50 Hz across three phases. At a power factor of 0.8 this works out to 577 A in standby duty and 520 A in continuous operation. Windings use class H insulation and the enclosure carries IP23 protection. Having 400 V three phase and 230 V phase-to-neutral together lets motor loads, lighting and socket circuits be fed from one distribution board.
- Standby power: 400 kVA / 320 kW / 577 A
- Prime power: 360 kVA / 288 kW / 520 A
- Engine: SDEC SC13H425D2, six cylinders, inline, 12.8 L
- Bore x stroke: 128 x 153 mm, compression ratio 16:1
- Aspiration: turbocharged aftercooled
- Fuel consumption: 85 L/h at 100% load, 63.7 L/h at 75% load
- Voltage and frequency: 400/230 V, 50 Hz, 3 phase, 0.8 power factor
- Class H insulation, IP23 protection
Installation and Use
In canopied form the unit measures 4000 x 1400 x 2100 mm (L x W x H); the open-type version takes a 3000 x 1400 mm footprint. The canopy suits outdoor placement, while the open frame fits plants that already have a generator room. The product is listed under stock code NDX-SDF-400, originates from Türkiye and carries a 24-month warranty.