Image is for illustration purposes only.
Baudouin Generators
Baudouin 250 kVA Diesel Generator
The Baudouin 250 kVA diesel generator delivers 250 kVA / 200 kW standby and 227 kVA / 181 kW prime power at a 0.8 power factor. Its 6-cylinder, 9.73-litre turbocharged aftercooled Baudouin 6M16G250/5 engine drives a three-phase alternator rated 400/230 V at 50 Hz.
- Standby Power (ESP)
- 250kVA· 200 kW
- Prime Power (PRP)
- 227kVA· 181 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 250 kVA / 200 kW / 361 A
- Prime Power (PRP)
- 227 kVA / 181 kW / 328 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Baudouin
- Engine Model
- 6M16G250/5
- Cylinders
- 6 / Inline
- Displacement
- 9.73 L
- Bore x Stroke
- 126 x 130 mm
- Compression Ratio
- 17:1
- Aspiration
- Turbocharged Aftercooled
- Cooling System Capacity
- 44
- Fuel Consumption (100% load)
- 48.7 L/h
- Fuel Consumption (75% load)
- 36.5 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 3700 x 1200 x 1900 mm
- Open Type (L x W)
- 2800 x 1200 mm
Product Information
- Category
- Baudouin Generators
- Stock Code
- NDX-BAU-250
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Baudouin 250 kVA Diesel Generator
What defines this set first is its electrical output. At a 0.8 power factor it is rated 250 kVA / 200 kW in standby duty (ESP) and 227 kVA / 181 kW in prime duty (PRP), so the load it carries as a backup source and the load it carries in continuous service are stated separately. On a 400/230 V system it supplies up to 361 A in standby and 328 A in prime duty, and those are the figures that decide breaker ratings and cable cross-sections.
Engine
Power comes from the BAUDOUIN 6M16G250/5 engine, a 6-cylinder inline unit of 9.73 litres with a 126 x 130 mm bore and stroke and a 17:1 compression ratio. A turbocharged aftercooled intake is what allows 200 kW to be drawn from that displacement. Fuel consumption is quoted at 48.7 L/h at 100% load and 36.5 L/h at 75% load, giving two reference points for costing a real duty cycle.
Alternator and Electrical Data
The alternator runs at 400/230 V, 50 Hz, three phase, with a 0.8 power factor. Windings use class H insulation and the housing carries an IP23 rating. Class H insulation withstands high winding temperatures, while IP23 guards against solid bodies and against water falling at an angle.
- Standby power (ESP): 250 kVA / 200 kW / 361 A
- Prime power (PRP): 227 kVA / 181 kW / 328 A
- Voltage and frequency: 400/230 V, 50 Hz, 3 phase
- Engine: BAUDOUIN 6M16G250/5, 6-cylinder inline, 9.73 L
- Intake: turbocharged aftercooled, 17:1 compression ratio
- Fuel consumption: 48.7 L/h at 100% load, 36.5 L/h at 75% load
- Insulation class H, protection class IP23
- Stock code: NDX-BAU-250
Installation and Use
The unit can be planned in a canopy or as an open set. Canopied dimensions are 3700 x 1200 x 1900 mm (L x W x H) and the open frame measures 2800 x 1200 mm (L x W), so the generator room or outdoor pad should be laid out to those figures. The product carries a 24-month warranty and is manufactured in Türkiye.