Image is for illustration purposes only.
Perkins Generator
Perkins 22 kVA Diesel Generator
The Perkins 22 kVA diesel generator delivers 22 kVA / 17.6 kW of standby power and 20 kVA / 16 kW of prime power. Built around the naturally aspirated 2.2 litre PERKINS 404A-22G1 engine, it supports 400/230 V, 50 Hz backup and continuous supply duties.
- Standby Power (ESP)
- 22kVA· 17.6 kW
- Prime Power (PRP)
- 20kVA· 16 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 22 kVA / 17.6 kW / 32 A
- Prime Power (PRP)
- 20 kVA / 16 kW / 29 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Perkins
- Engine Model
- 404A-22G1
- Cylinders
- 4 / Inline
- Displacement
- 2.2 L
- Bore x Stroke
- 84 x 100 mm
- Compression Ratio
- 23.3:1
- Aspiration
- Natural Aspiration
- Cooling System Capacity
- 7
- Fuel Consumption (100% load)
- 5.3 L/h
- Fuel Consumption (75% load)
- 3.9 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 2000 x 950 x 1260 mm
- Open Type (L x W)
- 1700 x 950 mm
Product Information
- Category
- Perkins Generator
- Stock Code
- NDX-PER-22
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Perkins 22 kVA Diesel Generator
In facilities where a dropped mains supply stops a production line, a cold chain or a server room, backup power is not a convenience but a condition of continuity. The Perkins 22 kVA diesel generator picks up critical loads the moment the grid fails, with 22 kVA / 17.6 kW of standby output, while its 20 kVA / 16 kW prime rating lets it serve as the main source on sites with no grid or an unstable one. The 400/230 V output matches the load profile of small industrial plants, commercial premises and irrigation systems.
Engine
At the core of the unit sits the 2.2 litre PERKINS 404A-22G1. The four-cylinder engine uses an inline layout, with a bore and stroke of 84 x 100 mm and a 23.3:1 compression ratio. It is naturally aspirated. Fuel consumption is 5.3 L/hour at 100% load and 3.9 L/hour at 75% load, which makes fuel planning predictable during long outages.
Alternator and Electrical Ratings
The alternator runs at 400/230 V and 50 Hz in a three-phase configuration, with a power factor of 0.8. The windings use class H insulation and the enclosure carries an IP23 protection rating. Current is 32 A in standby operation and 29 A in prime operation; these are the values for sizing the distribution panel and cable cross-section.
- Standby power (ESP): 22 kVA / 17.6 kW / 32 A
- Prime power (PRP): 20 kVA / 16 kW / 29 A
- Engine: PERKINS 404A-22G1, 4 cylinders, 2.2 L, naturally aspirated
- Voltage and frequency: 400/230 V, 50 Hz, 3 phase
- Insulation class H, protection class IP23, power factor 0.8
- Fuel consumption: 5.3 L/hour at 100% load, 3.9 L/hour at 75% load
- Canopy dimensions: 2000 x 950 x 1260 mm
- Stock code: NDX-PER-22
Installation and Use
In canopy form the unit measures 2000 x 950 x 1260 mm, while the open type occupies a 1700 x 950 mm footprint, making the choice between a generator room and an outdoor pad easier. The product originates from Türkiye and carries a 24-month warranty. It is listed in the Nidexa Jeneratör range under stock code NDX-PER-22.