Image is for illustration purposes only.
Perkins Generator
Perkins 50 kVA Diesel Generator
A 50 kVA diesel generator powered by a Perkins 1103A-33TG1 engine, rated 50 kVA / 40 kW in standby duty and 45 kVA / 36 kW in prime duty. Its three-phase alternator delivers 400/230 V at 50 Hz with class H insulation and IP23 protection.
- Standby Power (ESP)
- 50kVA· 40 kW
- Prime Power (PRP)
- 45kVA· 36 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 50 kVA / 40 kW / 72 A
- Prime Power (PRP)
- 45 kVA / 36 kW / 65 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Perkins
- Engine Model
- 1103A-33TG1
- Cylinders
- 3 / Inline
- Displacement
- 3.3 L
- Bore x Stroke
- 105 x 127 mm
- Compression Ratio
- 17.25:1
- Aspiration
- Turbocharged
- Cooling System Capacity
- 10.2
- Fuel Consumption (100% load)
- 10.7 L/h
- Fuel Consumption (75% load)
- 8.2 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 2300 x 950 x 1560 mm
- Open Type (L x W)
- 2000 x 950 mm
Product Information
- Category
- Perkins Generator
- Stock Code
- NDX-PER-50
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Perkins 50 kVA Diesel Generator (NDX-PER-50)
The Nidexa Perkins 50 kVA diesel generator is defined by its electrical output: 400/230 V, 50 Hz, three phases. It covers 50 kVA / 40 kW / 72 A in standby (ESP) duty and 45 kVA / 36 kW / 65 A in prime (PRP) duty. Every rating is referenced to a 0.8 power factor. On the alternator side, class H insulation and an IP23 protection rating set the thermal and physical limits of the electrical components.
Engine
Drive comes from a PERKINS 1103A-33TG1. The engine has 3 cylinders in an inline layout, a displacement of 3.3 litres, a bore and stroke of 105 x 127 mm and a compression ratio of 17.25:1. The induction type is turbocharged and the cooling capacity is given as 10.2. Fuel consumption is 10.7 L/h at 100% load and 8.2 L/h at 75% load.
Alternator and Electrical Ratings
The alternator produces 400/230 V at 50 Hz in three-phase form and is rated at a 0.8 power factor. Insulation is class H and protection is IP23. Rated current is 72 A in standby duty and 65 A in continuous duty. With 400 V line-to-line and 230 V line-to-neutral both available, three-phase motor loads and single-phase circuits run from the same set.
- Standby power (ESP): 50 kVA / 40 kW / 72 A
- Prime power (PRP): 45 kVA / 36 kW / 65 A
- Voltage and frequency: 400/230 V, 50 Hz, 3 phase, 0.8 power factor
- Engine: PERKINS 1103A-33TG1, 3 cylinders inline, 3.3 L, turbocharged
- Bore x stroke 105 x 127 mm, compression ratio 17.25:1
- Fuel consumption: 10.7 L/h at 100% load, 8.2 L/h at 75% load
- Class H insulation, IP23 protection, cooling capacity 10.2
- Model: Perkins 50 kVA, stock code NDX-PER-50
Installation and Use
Dimensions are given for both versions: the canopied set measures 2300 x 950 x 1560 mm (length x width x height), the open set 2000 x 950 mm (length x width). These figures can be used for layout planning and transport preparation. The country of origin is Türkiye and the warranty period is 24 months.