The Ricardo 90 kVA diesel generator delivers three-phase 400/230 V output at 50 Hz, rated 90 kVA / 72 kW / 130 A in standby and 82 kVA / 65.6 kW / 118 A in prime duty. Power comes from a turbocharged 6.49 L RICARDO R6105ZD six-cylinder diesel engine.

Standby Power (ESP)
90kVA· 72 kW
Prime Power (PRP)
82kVA· 65.6 kW
R6105ZDChina50 Hz400/230 V
Call Now

Technical Specifications

Power & Electrical

Standby Power (ESP)
90 kVA / 72 kW / 130 A
Prime Power (PRP)
82 kVA / 65.6 kW / 118 A
Voltage
400/230 V
Frequency
50 Hz
Phase
3
Power Factor
0.8

Engine

Engine Brand
Ricardo
Engine Model
R6105ZD
Cylinders
6 / Inline
Displacement
6.49 L
Bore x Stroke
105 x 125 mm
Compression Ratio
16:1
Aspiration
Turbocharged
Cooling System Capacity
25
Fuel Consumption (100% load)
19.8 L/h
Fuel Consumption (75% load)
14.8 L/h

Alternator

Voltage / Frequency
400/230 V - 50 Hz
Phase
3
Power Factor
0.8
Insulation Class
H
Protection Class
IP23

Dimensions

Canopied Type (L x W x H)
2850 x 1000 x 1420 mm
Open Type (L x W)
2100 x 1000 mm

Product Information

Category
Ricardo Generator
Stock Code
NDX-RIC-90
Warranty
24 months
Country of Origin
Türkiye

Overview

Ricardo 90 kVA Diesel Generator

The Nidexa Ricardo 90 kVA diesel generator is built around its electrical output: three-phase 400/230 V at 50 Hz. At a power factor of 0.8 it is rated 90 kVA, 72 kW and 130 A in standby (ESP) duty, and 82 kVA, 65.6 kW and 118 A in prime (PRP) duty. The gap between the two current ratings decides which figure switchgear and cable cross-sections should be sized against.

Engine

The set is driven by a RICARDO R6105ZD diesel engine. It is a six-cylinder inline unit with a displacement of 6.49 litres, a bore of 105 mm, a stroke of 125 mm and a compression ratio of 16:1. Aspiration is turbocharged. Fuel consumption is stated as 19.8 L/h at full load and 14.8 L/h at 75% load, giving two reference points for sizing fuel storage.

Alternator and Electrical Ratings

The alternator is rated 400/230 V at 50 Hz, three phases, power factor 0.8. The 400/230 V figure describes a connection arrangement in which three-phase and single-phase loads can be fed from the same set. Windings use class H insulation and the enclosure carries an IP23 protection rating. Line current is 130 A in standby duty and 118 A in prime duty.

  • Standby power (ESP): 90 kVA / 72 kW / 130 A
  • Prime power (PRP): 82 kVA / 65.6 kW / 118 A
  • Voltage and frequency: 400/230 V, 50 Hz, 3-phase, power factor 0.8
  • Engine: RICARDO R6105ZD, 6-cylinder inline, 6.49 L, turbocharged
  • Bore x stroke: 105 x 125 mm, compression ratio 16:1
  • Fuel consumption: 19.8 L/h at 100% load, 14.8 L/h at 75% load
  • Insulation class H, protection class IP23
  • Stock code: NDX-RIC-90

Installation and Operation

The set is specified in two body variants, canopied and open type. The canopied version measures 2850 x 1000 x 1420 mm (L x W x H), while the open-frame version measures 2100 x 1000 mm (L x W); plant room layout and service clearances should be planned around these figures. The IP23 rating requires assessing the site for water and dust exposure. The product is manufactured in Türkiye and carries a 24-month warranty.