Image is for illustration purposes only.
Ricardo Generator
Ricardo 75 kVA Diesel Generator
The Ricardo 75 kVA diesel generator delivers 75 kVA / 60 kW standby and 68 kVA / 54.4 kW prime power. A turbocharged RICARDO R4105IZLD engine, 4-cylinder inline and 4.33 L, feeds a 400/230 V, 50 Hz three-phase output.
- Standby Power (ESP)
- 75kVA· 60 kW
- Prime Power (PRP)
- 68kVA· 54.4 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 75 kVA / 60 kW / 108 A
- Prime Power (PRP)
- 68 kVA / 54.4 kW / 98 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Ricardo
- Engine Model
- R4105IZLD
- Cylinders
- 4 / Inline
- Displacement
- 4.33 L
- Bore x Stroke
- 105 x 125 mm
- Compression Ratio
- 16:1
- Aspiration
- Turbocharged
- Cooling System Capacity
- 18
- Fuel Consumption (100% load)
- 16.5 L/h
- Fuel Consumption (75% load)
- 12.3 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 2400 x 1000 x 1500 mm
- Open Type (L x W)
- 2100 x 1000 mm
Product Information
- Category
- Ricardo Generator
- Stock Code
- NDX-RIC-75
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Ricardo 75 kVA Diesel Generator
Sizing a generating set starts with separating two numbers: the peak a site draws in short bursts, and the load it carries hour after hour. The Ricardo 75 kVA covers both from a single frame, rated at 75 kVA / 60 kW standby (ESP) and 68 kVA / 54.4 kW prime (PRP). At a 0.8 power factor those ratings translate into 108 A standby and 98 A prime, so cable sizing and switchgear selection can be settled long before the unit reaches its foundation.
Engine
Power comes from a RICARDO R4105IZLD. It is a 4-cylinder inline engine of 4.33 L, with a 105 x 125 mm bore and stroke, a 16:1 compression ratio and turbocharged induction. Fuel consumption is quoted at 16.5 L/hour at 100% load and 12.3 L/hour at 75% load, which makes daily fuel budgeting straightforward once the duty cycle is known.
Alternator and Electrical Values
Alternator output is 400/230 V at 50 Hz across three phases, so three-phase machinery and 230 V single-phase circuits can both be served. Power factor is 0.8, insulation is class H and the protection rating is IP23. Working current is 108 A in standby operation and 98 A in prime operation.
- Standby (ESP) output: 75 kVA / 60 kW / 108 A
- Prime (PRP) output: 68 kVA / 54.4 kW / 98 A
- Engine: RICARDO R4105IZLD, 4-cylinder inline, 4.33 L, turbocharged
- Bore x stroke: 105 x 125 mm, compression ratio 16:1
- Voltage and frequency: 400/230 V, 50 Hz, 3-phase, power factor 0.8
- Insulation class H, protection class IP23
- Fuel use: 16.5 L/hour at 100% load, 12.3 L/hour at 75% load
- Stock code: NDX-RIC-75
Installation and Use
The set can be specified with a canopy or as an open frame. Canopied dimensions are 2400 x 1000 x 1500 mm (L x W x H) and the open type measures 2100 x 1000 mm (L x W), so the footprint and service clearances are worth measuring in advance. The generator originates from Türkiye and carries a 24-month warranty.