Image is for illustration purposes only.
Shanghai Dongfeng Generator
Shanghai Dongfeng 250 kVA Diesel Generator
The Shanghai Dongfeng 250 kVA diesel generator is built around a 6-cylinder, 8.8-litre SDEC SC9D250D2 engine delivering 250 kVA standby and 225 kVA prime power, with turbocharged aftercooled aspiration and a 400/230 V, 50 Hz three-phase output.
- Standby Power (ESP)
- 250kVA· 200 kW
- Prime Power (PRP)
- 225kVA· 180 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 250 kVA / 200 kW / 361 A
- Prime Power (PRP)
- 225 kVA / 180 kW / 325 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Shanghai Dongfeng
- Engine Model
- SC9D250D2
- Cylinders
- 6 / Inline
- Displacement
- 8.8 L
- Bore x Stroke
- 114 x 144 mm
- Compression Ratio
- 16.5:1
- Aspiration
- Turbocharged Aftercooled
- Cooling System Capacity
- 50
- Fuel Consumption (100% load)
- 52 L/h
- Fuel Consumption (75% load)
- 39 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 3400 x 1150 x 1750 mm
- Open Type (L x W)
- 2600 x 1150 mm
Product Information
- Category
- Shanghai Dongfeng Generator
- Stock Code
- NDX-SDF-250
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Shanghai Dongfeng 250 kVA Diesel Generator
What defines this set is first of all its mechanical layout. An inline six-cylinder SDEC block, fed by a turbocharger and an aftercooler, carries the high-compression diesel cycle a genset of this size depends on. The unit is rated at 250 kVA standby and 225 kVA prime, and the gap between those two figures is exactly the margin the engine keeps for itself once a site runs under continuous load.
Engine
The engine is an SDEC SC9D250D2. Its core mechanical data are a 6-cylinder inline arrangement, 8.8 L displacement, a 114 x 144 mm bore and stroke and a 16.5:1 compression ratio. Aspiration is turbocharged and aftercooled. Fuel consumption is given as 52 L/h at 100% load and 39 L/h at 75% load.
Alternator and Electrical Data
The alternator supplies 400/230 V at 50 Hz in a three-phase configuration, rated at a 0.8 power factor. Standby output is 250 kVA / 200 kW / 361 A, while continuous operation is rated at 225 kVA / 180 kW / 325 A. Winding insulation is class H and the protection rating is IP23.
- Standby power (ESP): 250 kVA / 200 kW / 361 A
- Prime power (PRP): 225 kVA / 180 kW / 325 A
- Engine: SDEC SC9D250D2, 6-cylinder, inline, 8.8 L
- Bore x stroke 114 x 144 mm, compression ratio 16.5:1
- Aspiration: turbocharged, aftercooled
- Output: 400/230 V, 50 Hz, 3-phase, power factor 0.8
- Insulation class H, protection class IP23
- Fuel consumption: 52 L/h at 100% load, 39 L/h at 75% load
Installation and Use
In canopy form the set measures 3400 x 1150 x 1750 mm, while the open-type version has a footprint of 2600 x 1150 mm. That difference is what drives the layout of the plant room or the concrete pad. The generator carries a 24-month warranty, is of Turkish origin and is listed under stock code NDX-SDF-250.