Yangdong 40 kVA Diesel Generator

The Yangdong 40 kVA diesel generator delivers three-phase output at 400/230 V and 50 Hz, rated 40 kVA / 32.8 kW in standby duty and 38 kVA / 30.4 kW in prime duty. Power comes from the turbocharged 3.8-litre, 4-cylinder YANGDONG Y4102ZLD diesel engine.

Standby Power (ESP)
40kVA· 32.8 kW
Prime Power (PRP)
38kVA· 30.4 kW
Y4102ZLDChina50 Hz400/230 V
Call Now

Technical Specifications

Power & Electrical

Standby Power (ESP)
40 kVA / 32.8 kW / 58 A
Prime Power (PRP)
38 kVA / 30.4 kW / 55 A
Voltage
400/230 V
Frequency
50 Hz
Phase
3
Power Factor
0.8

Engine

Engine Brand
Yangdong
Engine Model
Y4102ZLD
Cylinders
4 / Inline
Displacement
3.8 L
Bore x Stroke
102 x 118 mm
Compression Ratio
18:1
Aspiration
Turbocharged
Cooling System Capacity
13
Fuel Consumption (100% load)
9.8 L/h
Fuel Consumption (75% load)
7.3 L/h

Alternator

Voltage / Frequency
400/230 V - 50 Hz
Phase
3
Power Factor
0.8
Insulation Class
H
Protection Class
IP23

Dimensions

Canopied Type (L x W x H)
2000 x 950 x 1260 mm
Open Type (L x W)
1700 x 950 mm

Product Information

Category
Yangdong Generator
Stock Code
NDX-YAN-40
Warranty
24 months
Country of Origin
Türkiye

Overview

Yangdong 40 kVA Diesel Generator (NDX-YAN-40)

The electrical character of this set is defined by its three-phase output at 400/230 V and 50 Hz. In standby duty (ESP) it is rated at 40 kVA / 32.8 kW with a current of 58 A, while prime duty (PRP) settles at 38 kVA / 30.4 kW and 55 A. Both ratings are stated at a power factor of 0.8, so the available current follows directly from the declared kVA figure.

Engine

Mechanical power is supplied by the YANGDONG Y4102ZLD diesel engine, a four-cylinder inline unit of 3.8 litres with a bore and stroke of 102 x 118 mm and an 18:1 compression ratio. Turbocharged aspiration lets that displacement reach the declared output level. Fuel consumption is stated as 9.8 L/h at 100% load and 7.3 L/h at 75% load.

Alternator and Electrical Ratings

The alternator runs at 400/230 V and 50 Hz across three phases with a 0.8 power factor. Windings use class H insulation and the enclosure carries an IP23 protection rating. Output current reaches 58 A in standby operation and 55 A in continuous operation. The 400 V line-to-line and 230 V line-to-neutral levels allow three-phase motor loads and single-phase circuits to be fed from the same distribution board.

  • Standby power (ESP): 40 kVA / 32.8 kW / 58 A
  • Prime power (PRP): 38 kVA / 30.4 kW / 55 A
  • Voltage and frequency: 400/230 V, 50 Hz, 3 phase
  • Engine: YANGDONG Y4102ZLD, 4-cylinder inline, 3.8 L, turbocharged
  • Bore x stroke 102 x 118 mm, compression ratio 18:1
  • Fuel consumption: 9.8 L/h at 100% load, 7.3 L/h at 75% load
  • Class H insulation, IP23 protection, 0.8 power factor
  • Canopied 2000 x 950 x 1260 mm, open type 1700 x 950 mm

Installation and Use

In canopied form the set measures 2000 x 950 x 1260 mm (L x W x H), while the open version is listed at 1700 x 950 mm (L x W). The IP23 rating and the choice between canopy and open frame guide whether the unit is placed in an indoor room or in a sheltered outdoor position. Stock code NDX-YAN-40 is of Turkish origin and carries a 24-month warranty.