Skip to content
Nidexa Jeneratör
Call
Perkins 300 kVA Diesel Generator

Image is for illustration purposes only.

Perkins Generator

Perkins 300 kVA Diesel Generator

Powered by a Perkins 1506A-E88TAG4 engine, this Nidexa 300 kVA diesel generator delivers 300 kVA / 240 kW in standby and 275 kVA / 220 kW in prime operation. Its 400/230 V, 50 Hz three-phase output is available in canopy or open-frame form.

Standby Power (ESP)
300kVA· 240 kW
Prime Power (PRP)
275kVA· 220 kW
1506A-E88TAG4UK50 Hz400/230 V
Call Now

Technical Specifications

Power & Electrical

Standby Power (ESP)
300 kVA / 240 kW / 433 A
Prime Power (PRP)
275 kVA / 220 kW / 397 A
Voltage
400/230 V
Frequency
50 Hz
Phase
3
Power Factor
0.8

Engine

Engine Brand
Perkins
Engine Model
1506A-E88TAG4
Cylinders
6 / Inline
Displacement
8.8 L
Bore x Stroke
112 x 149 mm
Compression Ratio
16.1:1
Aspiration
Turbocharged Air-Air
Cooling System Capacity
29.6
Fuel Consumption (100% load)
60 L/h
Fuel Consumption (75% load)
45 L/h

Alternator

Voltage / Frequency
400/230 V - 50 Hz
Phase
3
Power Factor
0.8
Insulation Class
H
Protection Class
IP23

Dimensions

Canopied Type (L x W x H)
4000 x 1400 x 2100 mm
Open Type (L x W)
3000 x 1400 mm

Product Information

Category
Perkins Generator
Stock Code
NDX-PER-300
Warranty
24 months
Country of Origin
Türkiye

Overview

Perkins 300 kVA Diesel Generator (NDX-PER-300)

This 300 kVA class generator suits projects where the layout has to be fixed early. In canopy form the unit measures 4000 x 1400 x 2100 mm, so the space needed in a plant room or on an outdoor pad can be calculated before the order is placed. The open-frame version occupies a 3000 x 1400 mm footprint, which makes it easier to drop onto a prepared concrete base or into an existing generator room. Cable routes, exhaust outlets and ventilation openings can all be planned against these exact figures.

Engine

The power source is the 8.8 litre Perkins 1506A-E88TAG4 diesel engine. Its inline block carries 6 cylinders with a bore and stroke of 112 x 149 mm and a compression ratio of 16.1:1. Aspiration is turbocharged with air-to-air charge cooling (Turbocharged Air-Air). Fuel consumption is 60 L/h at 100% load and 45 L/h at 75% load, figures that feed directly into daily consumption and refuelling interval calculations.

Alternator and Electrical Values

Alternator output is 400/230 V at 50 Hz across 3 phases, rated at a 0.8 power factor. Standby (ESP) operation gives 300 kVA / 240 kW / 433 A, while prime (PRP) operation gives 275 kVA / 220 kW / 397 A. The windings use class H insulation and the enclosure carries an IP23 protection rating. Switchgear and cable sizing should be based on the 433 A standby current.

  • Standby power (ESP): 300 kVA / 240 kW / 433 A
  • Prime power (PRP): 275 kVA / 220 kW / 397 A
  • Engine: Perkins 1506A-E88TAG4, 6 cylinders inline, 8.8 L
  • Voltage and frequency: 400/230 V, 50 Hz, 3 phase
  • Class H insulation, IP23 protection rating
  • Fuel consumption: 60 L/h at 100% load, 45 L/h at 75% load

Installation and Use

The canopy version measures 4000 x 1400 x 2100 mm and the open-frame body has a 3000 x 1400 mm footprint, so handling and base preparation follow those dimensions. The unit carries a 24 month warranty, originates from Türkiye and is listed under stock code NDX-PER-300.

SEND ENQUIRY

Fill out the form and we will get back to you as soon as we can.

Enquiry Type

By submitting this form, you have read and agree to our Privacy Policy and Data Protection Notice.

WE ARE HERE TO HELP

Talk to an expert about the right generator for you.

Perkins 300 kVA Diesel Generator | Nidexa Jeneratör