Image is for illustration purposes only.
Perkins Generator
Perkins 400 kVA Diesel Generator
Built around the Perkins 2206A-E13TAG2 engine, the Nidexa NDX-PER-400 is rated at 400 kVA standby and 350 kVA prime power. It delivers 400/230 V, 50 Hz three phase output and measures 4500 x 1600 x 2200 mm in the canopy version.
- Standby Power (ESP)
- 400kVA· 320 kW
- Prime Power (PRP)
- 350kVA· 280 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 400 kVA / 320 kW / 577 A
- Prime Power (PRP)
- 350 kVA / 280 kW / 505 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Perkins
- Engine Model
- 2206A-E13TAG2
- Cylinders
- 6 / Inline
- Displacement
- 12.5 L
- Bore x Stroke
- 130 x 157 mm
- Compression Ratio
- 16.3:1
- Aspiration
- Turbocharged Air-Air
- Cooling System Capacity
- 51.4
- Fuel Consumption (100% load)
- 81 L/h
- Fuel Consumption (75% load)
- 62 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 4500 x 1600 x 2200 mm
- Open Type (L x W)
- 3300 x 1600 mm
Product Information
- Category
- Perkins Generator
- Stock Code
- NDX-PER-400
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Perkins 400 kVA Diesel Generator (NDX-PER-400)
When the site layout is drawn up, dimensions decide where this set can actually go. In the canopy version it occupies 4500 x 1600 x 2200 mm, while the open frame version drops to a 3300 x 1600 mm footprint. That gap drives the choice between an indoor generator room and an outdoor pad, and the 2200 mm height means door openings and overhead clearances should be measured beforehand.
Engine
Power comes from the Perkins 2206A-E13TAG2 engine. The 12.5 litre inline six cylinder block has a bore and stroke of 130 x 157 mm and a compression ratio of 16.3:1. Aspiration is turbocharged air to air. Fuel consumption is 81 L/hour at 100% load and 62 L/hour at 75% load, with a stated cooling capacity of 51.4.
Alternator and Electrical Values
Output is 400/230 V at 50 Hz across three phases, rated at a 0.8 power factor. In standby duty the set delivers 400 kVA / 320 kW and 577 A; in prime duty it delivers 350 kVA / 280 kW and 505 A. Winding insulation is class H and the protection rating is IP23.
- Standby power (ESP): 400 kVA / 320 kW / 577 A
- Prime power (PRP): 350 kVA / 280 kW / 505 A
- Engine: Perkins 2206A-E13TAG2, 6 cylinder inline, 12.5 L
- Voltage and frequency: 400/230 V, 50 Hz, 3 phase
- Insulation class H, protection class IP23
- Fuel consumption: 81 L/hour at 100% load, 62 L/hour at 75% load
- Canopy dimensions: 4500 x 1600 x 2200 mm
- Stock code: NDX-PER-400
Installation and Use
The canopy version suits outdoor placement, while the open frame version fits facilities that already have a generator room. Width stays at 1600 mm in both cases, so access corridor planning is identical. The unit carries a 24 month warranty and its country of origin is Türkiye.