Perkins Generator
Perkins 500 kVA Diesel Generator
Diesel generator powered by the Perkins 2506A-E15TAG2: six cylinders in line, 15.2 L displacement and turbocharged air-to-air aspiration, rated at 500 kVA standby and 450 kVA prime power. Output is 400/230 V, 50 Hz, three-phase.
- Standby Power (ESP)
- 500kVA· 400 kW
- Prime Power (PRP)
- 450kVA· 360 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 500 kVA / 400 kW / 722 A
- Prime Power (PRP)
- 450 kVA / 360 kW / 650 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Perkins
- Engine Model
- 2506A-E15TAG2
- Cylinders
- 6 / Inline
- Displacement
- 15.2 L
- Bore x Stroke
- 137 x 171 mm
- Compression Ratio
- 16:1
- Aspiration
- Turbocharged Air-Air
- Cooling System Capacity
- 58
- Fuel Consumption (100% load)
- 100 L/h
- Fuel Consumption (75% load)
- 76 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 4500 x 1600 x 2200 mm
- Open Type (L x W)
- 3300 x 1600 mm
Product Information
- Category
- Perkins Generator
- Stock Code
- NDX-PER-500
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Perkins 500 kVA Diesel Generator
The Perkins 500 kVA diesel generator is built around the mechanical architecture of the 2506A-E15TAG2 engine. Its 15.2-litre displacement is derived from a 137 mm bore and a 171 mm stroke, a long-stroke layout that puts the emphasis on torque production in the lower speed range. The 16:1 compression ratio and the turbocharged, air-to-air charge-cooled intake are the two elements that shape engine behaviour under load at the 500 kVA standby rating.
Engine
The Perkins 2506A-E15TAG2 has six cylinders in an inline arrangement. The 15.2 L displacement comes from bore and stroke figures of 137 x 171 mm, with a compression ratio of 16:1 and turbocharged air-to-air aspiration. Fuel consumption is stated as 100 L/h at 100% load and 76 L/h at 75% load. These figures serve as reference points when sizing the fuel tank to a site's daily running profile.
Alternator and Electrical Ratings
The alternator output is 400/230 V at 50 Hz, three-phase, calculated at a power factor of 0.8. In standby service (ESP) the set is rated at 500 kVA / 400 kW and 722 A; in prime service (PRP) the figures are 450 kVA / 360 kW and 650 A. Winding insulation is class H and the protection rating is IP23.
- Standby power (ESP): 500 kVA / 400 kW / 722 A
- Prime power (PRP): 450 kVA / 360 kW / 650 A
- Engine: Perkins 2506A-E15TAG2, 6 cylinders inline, 15.2 L
- Bore x stroke 137 x 171 mm, compression ratio 16:1
- Aspiration: turbocharged, air-to-air charge cooled
- Voltage and frequency: 400/230 V, 50 Hz, 3 phase, power factor 0.8
- Insulation class H, protection class IP23
- Fuel consumption: 100 L/h at 100% load, 76 L/h at 75% load
Installation and Operation
Canopied dimensions are 4500 x 1600 x 2200 mm (L x W x H), while the open-type version measures 3300 x 1600 mm (L x W), so the installation layout follows whichever configuration is chosen. The unit originates from Türkiye and the warranty period is 24 months. The model designation is Perkins 500 kVA and the stock code is NDX-PER-500.