Skip to content
Nidexa Jeneratör
Call
Perkins 66 kVA Diesel Generator

Image is for illustration purposes only.

Perkins Generator

Perkins 66 kVA Diesel Generator

Powered by the Perkins 1103A-33TG2 engine, this 66 kVA diesel generator delivers 60 kVA of prime power and burns 13.9 L/h at full load. Its 400/230 V, 50 Hz three-phase output suits facilities that need to budget running costs in advance.

Standby Power (ESP)
66kVA· 52.8 kW
Prime Power (PRP)
60kVA· 48 kW
1103A-33TG2UK50 Hz400/230 V
Call Now

Technical Specifications

Power & Electrical

Standby Power (ESP)
66 kVA / 52.8 kW / 95 A
Prime Power (PRP)
60 kVA / 48 kW / 87 A
Voltage
400/230 V
Frequency
50 Hz
Phase
3
Power Factor
0.8

Engine

Engine Brand
Perkins
Engine Model
1103A-33TG2
Cylinders
3 / Inline
Displacement
3.3 L
Bore x Stroke
105 x 127 mm
Compression Ratio
17.25:1
Aspiration
Turbocharged
Cooling System Capacity
10.2
Fuel Consumption (100% load)
13.9 L/h
Fuel Consumption (75% load)
10.4 L/h

Alternator

Voltage / Frequency
400/230 V - 50 Hz
Phase
3
Power Factor
0.8
Insulation Class
H
Protection Class
IP23

Dimensions

Canopied Type (L x W x H)
2300 x 950 x 1560 mm
Open Type (L x W)
2000 x 950 mm

Product Information

Category
Perkins Generator
Stock Code
NDX-PER-66
Warranty
24 months
Country of Origin
Türkiye

Overview

Perkins 66 kVA Diesel Generator

Fuel is the largest recurring cost across the life of any generating set, and the Perkins 66 kVA diesel generator is specified so that this cost can be worked out in advance. The set consumes 13.9 litres per hour at 100% load and 10.4 litres per hour at 75% load, a gap of 3.5 litres for every hour of operation. With 60 kVA of prime power and 66 kVA of standby power available, the load profile can be planned around the fuel budget rather than against it.

Engine

At the core of the set sits the PERKINS 1103A-33TG2, a three-cylinder inline diesel engine of 3.3 litres. Bore and stroke measure 105 x 127 mm and the compression ratio is 17.25:1. Turbocharged aspiration raises the air charge and supports combustion efficiency, which is the main reason the consumption figures stay at the stated level. Cooling capacity is given as 10.2.

Alternator and Electrical Ratings

The alternator provides a three-phase output at 400/230 V and 50 Hz. At a power factor of 0.8 this works out to 95 A in standby operation and 87 A in prime operation. The windings use class H insulation and the housing carries an IP23 protection rating.

  • Standby power (ESP): 66 kVA / 52.8 kW / 95 A
  • Prime power (PRP): 60 kVA / 48 kW / 87 A
  • Engine: PERKINS 1103A-33TG2, 3 cylinders, 3.3 L, turbocharged
  • Voltage and frequency: 400/230 V, 50 Hz, 3 phase
  • Fuel consumption: 13.9 L/h at 100% load, 10.4 L/h at 75% load
  • Insulation class H, protection class IP23
  • Canopied dimensions: 2300 x 950 x 1560 mm
  • Warranty 24 months, made in Türkiye

Installation and Use

The canopied version measures 2300 x 950 x 1560 mm, while the open type frame is 2000 x 950 mm. That gives the option of installing the set as an open unit inside a plant room or as a canopied unit outdoors. The product carries the stock code NDX-PER-66, is manufactured in Türkiye and comes with a 24 month warranty.

SEND ENQUIRY

Fill out the form and we will get back to you as soon as we can.

Enquiry Type

By submitting this form, you have read and agree to our Privacy Policy and Data Protection Notice.

WE ARE HERE TO HELP

Talk to an expert about the right generator for you.