Image is for illustration purposes only.
Perkins Generator
Perkins 165 kVA Diesel Generator
A 165 kVA diesel generator built around the Perkins 1106A-70TAG2 engine, rated at 165 kVA / 132 kW standby and 150 kVA / 120 kW prime power. Its 400/230 V, 50 Hz three-phase output and class H insulation cover continuous loads and motor starting peaks alike.
- Standby Power (ESP)
- 165kVA· 132 kW
- Prime Power (PRP)
- 150kVA· 120 kW
Technical Specifications
Power & Electrical
- Standby Power (ESP)
- 165 kVA / 132 kW / 238 A
- Prime Power (PRP)
- 150 kVA / 120 kW / 217 A
- Voltage
- 400/230 V
- Frequency
- 50 Hz
- Phase
- 3
- Power Factor
- 0.8
Engine
- Engine Brand
- Perkins
- Engine Model
- 1106A-70TAG2
- Cylinders
- 6 / Inline
- Displacement
- 7 L
- Bore x Stroke
- 105 x 135 mm
- Compression Ratio
- 18.2:1
- Aspiration
- Turbocharged Air-Air
- Cooling System Capacity
- 21
- Fuel Consumption (100% load)
- 33.4 L/h
- Fuel Consumption (75% load)
- 24.7 L/h
Alternator
- Voltage / Frequency
- 400/230 V - 50 Hz
- Phase
- 3
- Power Factor
- 0.8
- Insulation Class
- H
- Protection Class
- IP23
Dimensions
- Canopied Type (L x W x H)
- 3400 x 1150 x 1750 mm
- Open Type (L x W)
- 2500 x 1150 mm
Product Information
- Category
- Perkins Generator
- Stock Code
- NDX-PER-165
- Warranty
- 24 months
- Country of Origin
- Türkiye
Overview
Perkins 165 kVA Diesel Generator (NDX-PER-165)
Sizing a generator comes down to separating the load a facility draws continuously from the peaks that appear when motors and compressors start. The Perkins 165 kVA answers both in a single frame, with 150 kVA / 120 kW of prime power (PRP) for uninterrupted duty and 165 kVA / 132 kW of standby power (ESP) for backup service. Continuous circuits are planned around 217 A, while short-term standby scenarios allow up to 238 A.
Engine
Power comes from the Perkins 1106A-70TAG2 diesel engine, a 6-cylinder inline unit of 7 L displacement. A 105 x 135 mm bore and stroke together with an 18.2:1 compression ratio favour strong torque at low engine speed, and the turbocharged air-to-air aspiration cools the charge air before combustion. Fuel consumption is 33.4 L/h at 100% load and 24.7 L/h at 75% load, which makes tank sizing straightforward.
Alternator and Electrical Data
The alternator delivers 400/230 V at 50 Hz across three phases, rated at a 0.8 power factor, so three-phase motor loads and single-phase consumers can be distributed from the same source. Winding insulation is class H and the enclosure carries IP23 protection. Available current is 217 A in prime duty and 238 A in standby duty.
- Standby power (ESP): 165 kVA / 132 kW / 238 A
- Prime power (PRP): 150 kVA / 120 kW / 217 A
- Engine: Perkins 1106A-70TAG2, 6-cylinder inline, 7 L
- Aspiration: turbocharged air-to-air, 18.2:1 compression ratio
- Output: 400/230 V, 50 Hz, 3 phase, 0.8 power factor
- Class H insulation, IP23 enclosure protection
- Fuel consumption: 33.4 L/h at 100% load, 24.7 L/h at 75% load
Installation and Operation
The canopied version measures 3400 x 1150 x 1750 mm, while the open-type skid measures 2500 x 1150 mm, a difference worth checking against the floor area you have. The IP23 rating suits properly ventilated machine rooms. The generator originates from Türkiye and is covered by a 24-month warranty. Stock code: NDX-PER-165.